Description
Physical Characteristics
- Conductor: Stranded Bare Copper
- Number of Conductors: 3
- Size: 18 AWG
- Strand Count: 19/30 AWG Stranded
- Insulation:Plenum Polyolefin (Low Smoke, Flame-Retardant & RoHS Compliant)
- Conductor Color Code: 1. Black 2. Red 3. White
- Rip Cord: Applied longitudinally under jacket
- Jacket: Plenum PVC (Low-Smoke, Flame-Retardant & RoHS Compliant)
- Nominal Cable Diameter (in): 0.20
- Nominal Cable Net Weight (lbs/1000ft): 25
- Minimum Bend Radius (in): 3.0
- Maximum Pulling Force (lbs): 35
- Temperature Rating (°F)
Installation: +32 to +140
Storage & Operation: -4 to +167
ISO9001: 2008, ISO14001: 2004
Standard Compliances
- NEC: 725 & 800
- UL Standard: UL 13 & UL 444
- Flame Rating:UL 910 Plenum, NFPA 262, c(UL) FT6
- RoHS: Compliant Directive 2011/65/EU
Electrical Characteristics
- Operating Voltage: 300 Volts Max
- Capacitance: 29.4 pF/ft Nom
- Impedance: 35 Ohms Nom
- DC Resistance: 7.02 Ohms/M’ @ +68 °F